Parameter automatic setting
When parameters are set using parameter automatic setting, the set parameters are saved in the CC-Link IE TSN master
station. Those parameters are read from the CC-Link IE TSN master station and set automatically when the NZ2GN-GFB
performs data link.
The parameters automatically set from the CC-Link IE TSN master station are also stored in the non-volatile memory in the
NZ2GN-GFB.
When replacing the NZ2GN-GFB due to module failure or other reasons, the parameters that were set using parameter
automatic setting are set in the new module.
If the parameters saved in the CC-Link IE TSN master station are the same as the parameters saved in the
non-volatile memory in the NZ2GN-GFB during parameter automatic setting, the parameters in the non-
volatile memory in the NZ2GN-GFB are not overwritten.
The error in the NZ2GN-GFB is cleared when the NZ2GN-GFB parameters are changed using parameter
automatic setting.
Procedure
1.
Open the "CC-Link IE TSN Configuration" window.
[Navigation window] [Parameter] [Module Information] Model name [Basic Settings] [Network Configuration
Settings]
2.
Select the NZ2GN-GFB in "Module List" and drag it to the list of stations or the network map.
3.
Select the station type of CC-Link IE Field Network in "Station-specific mode setting".
6 PARAMETER SETTINGS
6.3 Module Parameter Setting
6
57