Mitsubishi Electric CC-Link IE TSN User Manual page 45

Field network bridge module
Table of Contents

Advertisement

Network Configuration Settings
The following shows the NZ2GN-GFB items set in network configuration settings.
■Setting procedure
1.
Open the "CC-Link IE TSN Configuration" window from the parameter of the CC-Link IE TSN master station.
[Navigation window]  [Parameter]  [Module Information]  Model name  [Basic Settings]  [Network Configuration
Settings]
2.
Select the NZ2GN-GFB in "Module List" and drag it to the list of stations or the network map.
3.
An assignment setting row is added to the station list, the total number of stations is increased, and the selected module
is added to the network map.
4.
Set items in the station list if necessary.
5.
Click the [Close with Reflecting the Setting] button to complete the setting process and close the window.
Before setting an item for the NZ2GN-GFB, set "Station-specific mode setting" first. Changing the "Station-
specific mode setting" returns some setting items to the initial value.
■Setting item
Item
STA#
Station Type
*3
RX Setting, RY Setting
Points
Start
End
*3
RWw Setting, RWr Setting
Points
Start
End
IP Address
Setting
Sets the NZ2GN-GFB station number.
Sets the station type.
Sets the assignment of RX, RY points.
Sets the start number of RX, RY.
Sets the end number of RX and RY points.
Sets the assignment of RWw, RWr points.
Sets (the number used) + 32 for the NZ2GN-GFB.
Sets the start number of RWw, RWr.
Sets the end number of RWw and RWr points.
Sets the IP address of CC-Link IE TSN on the NZ2GN-GFB.
The default values are as follows:
• First to third octet: Same as the CC-Link IE TSN master station
• Fourth octet: Automatically set between 1 to 254, from the smallest
number available
Setting range
*1*2
1 to 120
(Default: Serial number of the added
station)
Fixed to "Remote Station".
0 to 16384
(Default: 16)
0000 to 3FF0
(Default: 0000)
000F to 3FFF
(Default: 000F)
0 to 2080
(Default: 40)
0000 to 1FFC
(Default: 0000)
0003 to 1FFF
(Default: 0027)
0.0.0.1 to 223.255.255.254
(Default: As described on the left)
6 PARAMETER SETTINGS
6.1 Parameter Settings for CC-Link IE TSN
6
43