Cyclic Transmission Stop And Restart - Mitsubishi Electric CC-Link IE TSN User Manual

Field network bridge module
Table of Contents

Advertisement

Cyclic transmission stop and restart

This function allows users to select a CC-Link IE Field Network connected station and stop the cyclic transmission during
debugging and other operations. (Data will not be received from a device station nor transmitted from own station.)
It also restarts stopped cyclic transmissions. Transient transmission does not stop.
The cyclic transmission of any station can be stopped and restarted when the NZ2GN-GFB is used as the CC-
Link IE Field Network master station.
The cyclic transmission of own station can be stopped and restarted when the NZ2GN-GFB is used as the
CC-Link IE Field Network local station.
Setting method
Cyclic transmissions can be stopped and restarted using the following methods.
Item
"Link Start/Stop" of "CC-Link IE TSN/CC-Link IE
Field Diagnostics"
Remote buffer memory
Precautions
When the link special relay (SB) that instructs the CC-Link IE Field Network master station or the target station to start/stop
the link is on (Startup or stop requested), it may not be possible to start/stop the link from the CC-Link IE Field Network
diagnostics window.
When executing link start/stop from the CC-Link IE Field Network diagnostics window, turn off (Startup or stop not requested)
the link special relay (SB) that instructs link start/stop.
Reference
Page 121 CC-Link IE Field Network diagnostics
Page 223 Details of remote buffer memory (Link special relay (SB) area of CC-Link IE Field
Network)
Page 241 Details of remote buffer memory (Link special register (SW) area of CC-Link IE Field
Network)
7 FUNCTIONS
77
7.1 Cyclic Transmission
7

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cc-link ie

Table of Contents