Network No. match status (200FH.b8)
Indicates the network No. match status of each station.
• Off: Network No. match in all stations
• On: Network No. mismatch station exists
When this relay is turned, the status of each station can be checked with 'Network No. match status' (30F8H to 30FFH).
Depending on the update timing, 'Network No. match status' (30F8H to 30FFH) may not be updated immediately.
Condition
Enabled when 'Baton pass status of own station' (2004H.b7) is off.
CPU operating status of station No.0 (200FH.b15)
Stores the operating status of the CPU module on station No.0.
• Off: RUN state
• On: STOP state, PAUSE state, or moderate/major error
*1 Stores the moderate/major error occurrence status when the NZ2GN-GFB is used as the CC-Link IE Field Network master station.
CPU moderate/major error status of each station (2010H.b0)
Stores the moderate/major error or stop error occurrence status of each station.
Stores the moderate/major error occurrence status of the module when the target station is the NZ2GN-GFB.
• Off: No moderate/major error (stop error)
• On: Station with a moderate/major error (stop error) exists
When this relay is turned on, the status of each station can be checked with 'CPU moderate/major error status of each station'
(3100H to 3107H).
Depending on the update timing, 'CPU moderate/major error status of each station' (3100H to 3107H) may not be updated
immediately.
Condition
Enabled when 'Baton pass status of own station' (2004H.b7) is off. When 'Baton pass status of own station' (2004H.b7) is turned on (error), data from
immediately before the error is held.
*1 When the NZ2GN-GFB is used as the CC-Link IE Field Network master station, this relay area is also turned on when the CPU module
of the CC-Link IE TSN master station has a moderate/major error.
CPU moderate/major error status of master station (2010H.b1)
Stores the moderate/major error occurrence status of the CPU module on the master station (master operation station).
• Off: No moderate/major error
• On: Moderate/major error
Condition
Enabled when 'Baton pass status of own station' (2004H.b7) is off. When 'Baton pass status of own station' (2004H.b7) is turned on (error), data from
immediately before the error is held.
*1 When the NZ2GN-GFB is used as the CC-Link IE Field Network master station, this relay area is also turned on when the CPU module
of the NZ2GN-GFB or CC-Link IE TSN master station has a moderate/major error.
*1
*1
Appendix 3 Remote Buffer Memory
A
*1
APPX
233