Error code
Error definition and causes
D203H
The read data or write address of the transient
transmission is incorrect.
D204H
The network number of transient transmission is
incorrect.
D205H
The target station number of transient transmission
is incorrect.
D206H
The network number of transient transmission is
incorrect.
D207H
In transient transmission, there are over seven
relays to other networks.
D208H
The network number of transient transmission is
incorrect.
D209H to D20AH
The target station number of transient transmission
is incorrect.
D20BH to D20CH
There was no master station when the specified
master station was specified for transient
transmission.
D20DH
Transmission completion wait timeout has occurred
in transient data transmission.
D20EH
The header information of transient transmission is
incorrect.
D20FH
In transient transmission, the command which
cannot be requested to all or a group of stations was
executed with all stations specification or group
specification.
D210H
The target station number of transient transmission
is incorrect.
D212H
Transient transmission sending has failed.
D213H
• The command of transient transmission is
incorrect.
• The CC-Link IE Field Network diagnostics was
used for the network to which the relay receiving
station belongs.
D214H
The data length of transient transmission is
incorrect.
D216H to D217H
The command of transient transmission is incorrect.
D218H
The number of read/write data of transient
transmission is incorrect.
D219H
The attribute code of transient transmission is
incorrect.
D21AH
The access code of transient transmission is
incorrect.
Action
Correct the read data or write address at the transient request source, and retry the
operation.
• Correct the network number at the transient request source, and retry the
operation.
• If the request source is on another network, check if "Routing Setting" are
correctly set.
Correct the target station number at the transient request source, and retry the
operation.
• Correct the network number at the transient request source, and retry the
operation.
• If the request source is on another network, check if "Routing Setting" are
correctly set.
• Change the system configuration so that the number of relay stations may be
seven or less.
• Check if "Routing Setting" are correctly set.
• Correct the network number at the transient request source, and retry the
operation.
• If the request source is on another network, check if "Routing Setting" are
correctly set.
Correct the target station number at the transient request source, and retry the
operation.
Correct the target station number at the transient request source, and retry the
operation.
• Check the network status using the CC-Link IE Field Network diagnostics of the
engineering tool, and take action.
• When the own station, target station, or relay station detected an error, identify
the cause of the error and take action.
• Lower the transient transmission usage frequency, and then perform again.
• When "Communication Mode" in "Application Settings" of the master station
(submaster station) is set to "High-Speed", change it to "Normal" and retry the
operation.
• Check if the switching hub and the cables of the request source are connected
properly.
Correct the header information at the transient request source, and retry the
operation.
Check that the command can be requested to all or a group of stations at the
transient request source, and retry the operation.
Correct the header information at the transient request source, and retry the
operation.
• Check if the switching hub and the cables of the request source are connected
properly.
• Connect the cable to the other port on the request source, and retry the
operation.
• Lower the transient transmission usage frequency, and then perform again.
• Correct the request command at the transient request source, and retry the
operation.
• Review the connection destination so that the CC-Link IE Field Network
diagnostics is used for the network to which the relay sending station belongs.
Correct the data length at the transient request source, and retry the operation.
Correct the request command at the transient request source, and retry the
operation.
Correct the number of read or write device data at the transient request source,
and retry the operation.
Correct the attribute code at the transient request source, and retry the operation.
Correct the access code at the transient request source, and retry the operation.
10 TROUBLESHOOTING
161
10.7 Error Code List