Mitsubishi Electric CC-Link IE TSN User Manual page 184

Field network bridge module
Table of Contents

Advertisement

Data link status of each station on CC-Link IE Field Network (RWr18 to RWr1F)
This area is used to check the data link status of each station of CC-Link IE Field Network.
Stores the data link status of each station in each bit.
• Off: Data link normal station
• On: Data link faulty station
Address
b15
RWr18
16
RWr19
32
RWr1A
48
RWr1B
64
RWr1C
80
RWr1D
96
RWr1E
112
RWr1F
Each number in the table represents a station number.
 is fixed to 0.
This flag is enabled when 'Baton pass status of own station' (RWr6.b0) is off (normal). When it is turned on (faulty), the data
prior to the error is retained. ( Page 180 Baton pass status of own station (RWr6.b0))
• If multiple stations change from faulty to normal, they are reconnected to the network one by one per link
scan, so the time until the status changes to off (data link normal station) may vary by several seconds.
• If no response is received for several link scans, the station is determined to be a data link faulty station.
• Reserved stations and stations higher than the maximum station number are ignored.
• Depending on the update timing, the timing to retain and clear remote I/O signals from I/O maintenance
settings may differ.
APPX
182
Appendix 2 Remote Register
b14
b13
b12
b11
15
14
13
12
31
30
29
28
47
46
45
44
63
62
61
60
79
78
77
76
95
94
93
92
111
110
109
108
b10
b9
b8
b7
11
10
9
8
27
26
25
24
43
42
41
40
59
58
57
56
75
74
73
72
91
90
89
88
107
106
105
104
120
b6
b5
b4
b3
7
6
5
4
23
22
21
20
39
38
37
36
55
54
53
52
71
70
69
68
87
86
85
84
103
102
101
100
119
118
117
116
b2
b1
b0
3
2
1
19
18
17
35
34
33
51
50
49
67
66
65
83
82
81
99
98
97
115
114
113

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cc-link ie

Table of Contents