Mitsubishi Electric CC-Link IE TSN User Manual page 216

Field network bridge module
Table of Contents

Advertisement

Station No. (CC-Link IE TSN station No. <-> IP address conversion setting No.1 to 120)
■Address
CC-Link IE TSN station No. <-> IP address conversion setting
No.
No.1
No.2
No.3
No.120
■Description
This address is used to set the station number of the other station on CC-Link IE TSN that is a request station, relay station, or
destination station when communicating between different networks with the NZ2GN-GFB as a relay station.
For details, refer to the following.
Page 55 CC-Link IE TSN station No. <-> IP address conversion setting
If the setting No. used for setting the station No. exceeds the number of units set in 'Valid number of "CC-Link IE TSN station
No. <-> IP address conversion setting"' (0129H), the set value is not reflected and ignored.
■Setting value
b15
b14
b13
*1
Fixed to 0
*1 A value set in bit 7 to bit 15 is ignored.
Setting value
0000H
0001H
0078H
To enable a set parameter, refer to the following.
Page 184 Operation condition setting request flag (RWw0.b9)
• If a value outside the configurable range is written and the 'Operating condition setting request flag'
(RWw0.b9) is turned on, an error (error code: 028CH) occurs and all parameters are not saved in the non-
volatile memory of the NZ2GN-GFB. Set it again after correcting the value.
• If the station numbers overlap, an error (error code: 0296H) occurs and all parameters are not saved in the
non-volatile memory of the NZ2GN-GFB. Set it again after correcting the value.
APPX
214
Appendix 3 Remote Buffer Memory
b12
b11
b10
b9
Address
0200H
0203H
0206H
0365H
b8
b7
b6
b5
Setting value
Station number
0
1
120
b4
b3
b2
b1
b0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cc-link ie

Table of Contents