When the NZ2GN-GFB is used as the CC-Link IE Field Network master station (2)
The following image indicates the transmission delay time for communication between CC-Link IE TSN master station and
CC-Link IE Field Network local stations.
CC-Link IE TSN
CPU module
master module
Device
Link device
(2)
(1)
Master station
The transmission delay time is the total of (1) to (7).
No.
Description
(1)
CC-Link IE TSN master station sequence scan time
(2)
CC-Link IE TSN master station link refresh time
(3)
CC-Link IE TSN cyclic data transfer processing time
(communication cycle interval)
(4)
NZ2GN-GFB device transfer time
(5)
CC-Link IE Field Network link scan time
(6)
CC-Link IE Field Network local station link refresh time
(7)
CC-Link IE Field Network local station sequence scan time
For details on calculating (1) + (2) + (3), refer to the user's manual for the CC-Link IE TSN master station
used.
The following shows the variables used to calculate the transmission delay time.
Variable
Description
Tb
NZ2GN-GFB device transfer time
LS_field
CC-Link IE Field Network link scan time
SL_field
CC-Link IE Field Network local station sequence scan time (including link refresh time)
(LS_field  m_field)  SL_field (round up the calculated value to the nearest integer)
n_field
(SL_field  LS_field) (round up the calculated value to the nearest integer)
n3_field
(SL_field  (LS_field  m_field)) (round up the calculated value to the nearest integer)
k_field
m_field
Constant value based on the number of RWw assignment points of CC-Link IE Field Network local stations
• 0 to 256 words: 1
• 257 to 512 words: 2
• 513 to 768 words: 3
• 769 to 1024 words: 4
NZ2GN-GFB
Link device
(4)
(3)
Remote station
CC-Link IE TSN
CC-Link IE Field
Network
local module
Link device
Link device
(5)
Master station
Local station
CC-Link IE Field Network
Reference
 User's manual for the CPU module used
 User's manual for the CC-Link IE TSN master station used
Page 266 Device transfer time
Page 266 Link scan time
 User's manual for the CPU module used
Appendix 4 Processing Time
CPU module
Device
(6)
(7)
A
APPX
269