Setting range
Set the value from 1 to 254.
When the value from 1 to 254 is set, the result is as follows.
• The first to third octets of the IP address: The first to third octets from the IP address of the CC-Link IE TSN master station
are used for operation. The fourth octet uses the CC-Link IE TSN IP address setting switch value for operation.
• Subnet mask: The subnet mask of the CC-Link IE TSN master station is used for operation.
If a value other than 1 to 254 is set, the following will occur.
• When 0 is set, the IP address saved in the non-volatile memory and the subnet mask of the CC-Link IE TSN master station
are used for operation.
• When 255 is set, an error (error code: 0106H) occurs.
• Do not change the CC-Link IE TSN IP address setting switch when the NZ2GN-GFB is turned on. Doing so
causes an error (error code: 0200H) to occur and the ERR. LED to turn on. Return the CC-Link IE TSN IP
address setting switch to its previous position and turn on 'Error clear request flag' (RWw0.b10) to clear the
error and turn off the ERR. LED.
• When the power is turned on with the CC-Link IE TSN IP address setting switch set to a value in the range
of 1 to 254, the IP address is saved in the non-volatile memory when a data link with the CC-Link IE TSN
master station is established. As the factory default, 192.168.3.250 is set for the non-volatile memory.
• Set the IP address in a way that the fourth octet is not duplicated in the access range of CC-Link IE TSN. If
duplicated, the IP address will be duplicated due to the automatic setting of the first to third octet of the IP
address, and data link will not be established.
The following IP addresses cannot be used for the NZ2GN-GFB.
• IP addresses whose host addresses are all 0 or 255.
• IP address whose third octet and fourth octet are all 255
• IP address whose range is outside 0.0.0.1 to 223.255.255.254
Precautions
When operating the switch, use a static eliminating product or antistatic driver or touch a conducting object such as a
grounded metal to discharge the static electricity from the human body. Failure to do so may cause the module to fail or
malfunction.