Settings for CC-Link IE Field Network station number setting
switch
Set the CC-Link IE Field Network station number using the CC-Link IE Field Network station number setting switches on the
front of the NZ2GN-GFB. The setting of CC-Link IE Field Network station number setting switch is enabled when the NZ2GN-
GFB is powered on, so set this function when the module is powered off.
When operating the CC-Link IE Field Network station number setting switch, use a flathead screwdriver with a
blade width of 2.5mm or less.
Setting method
Set the station number using the CC-Link IE Field Network station number setting switch x1 and x16 (hexadecimal).
The setting method is the same as for the CC-Link IE TSN IP address setting switch. ( Page 26 Setting method)
Setting range
■When the NZ2GN-GFB is used as the CC-Link IE Field Network master station
Set the station number to 0.
When another value is set, an error (error code: 0113H) occurs.
■When the NZ2GN-GFB is used as the CC-Link IE Field Network local station
Set the station number to 1 to 120.
When a value other than 1 to 120 is set, an error (error code: 0114H) occurs.
• For details on the station type setting of CC-Link IE Field Network of the NZ2GN-GFB, refer to the following.
Page 47 Module Parameter Setting
• Do not change the CC-Link IE Field Network station number setting switch when the NZ2GN-GFB is ON.
Doing so causes an error (error code: 0201H) to occur and the ERR. LED to flash. Return the CC-Link IE
Field Network station number setting switch to its previous position and turn on 'Error clear request flag'
(RWw0.b10) to clear the error and turn off the ERR. LED.
• If the CC-Link IE Field Network station number setting switch is outside the setting range, the NZ2GN-GFB
does not perform data link on CC-Link IE Field Network.
Precautions
When operating the switch, use a static eliminating product or antistatic driver or touch a conducting object such as a
grounded metal to discharge the static electricity from the human body. Failure to do so may cause the module to fail or
malfunction.