Mitsubishi Electric CC-Link IE TSN User Manual page 232

Field network bridge module
Table of Contents

Advertisement

PORT current error frame reception status of own station (2) (2008H.b12)
Indicates if there is a receive frame error line status warning level for the current status in the PORT of own station.
• Off: There is no receive frame error line status warning level.
• On: There is a receive frame error line status warning level.
PORT error frame reception detection status of own station (latch) (2) (2008H.b14)
Indicates if there was a receive frame error line status warning level in the PORT of own station since turning on the power.
• Off: There is no receive frame error line status warning level.
• On: There was a receive frame error line status warning level.
Network configuration mismatch occurrence status (2009H.b8)
Stores the match or mismatch status of the actual network configuration and the network map of the CC-Link IE Field Network
diagnostics when the NZ2GN-GFB is used as the CC-Link IE Field Network master station.
• Off: Match
• On: Mismatch
After the return of the device station, it may be turned on regardless of the actual match/mismatch status.
Usage is prohibited when the NZ2GN-GFB is used as the CC-Link IE Field Network local station.
Number of connected modules over occurrence status (2009H.b9)
Indicates if the number of device stations connected to the master station is 32 or less, or 33 or more when the NZ2GN-GFB
is used as the CC-Link IE Field Network master station.
The number of connected modules is the total of device stations that are currently connected and those that were previously
connected.
• Off: 32 or less
• On: 33 or more
Usage is prohibited when the NZ2GN-GFB is used as the CC-Link IE Field Network local station.
Baton pass error status of each station (200AH.b0)
Stores the baton pass status of each station.
• Off: All stations normal
• On: Faulty station exists
When there is a faulty station, the status of each station can be checked with 'Baton pass status of each station' (30A0H to
30A7H).
Depending on the link refresh timing, 'Baton pass status of each station' (30A0H to 30A7H) may not be updated immediately.
Condition
• Enabled when 'Baton pass status of own station' (2004H.b7) is off. When 'Baton pass status of own station' (2004H.b7) is turned on (error), data from
immediately before the error is held.
• Reserved stations and stations higher than the maximum station number are ignored.
Baton pass error status of master station (200AH.b1)
Stores the baton pass status of the master station (master operating station).
• Off: Normal
• On: Error
Condition
Enabled when 'Baton pass status of own station' (2004H.b7) is off. When 'Baton pass status of own station' (2004H.b7) is turned on (error), data from
immediately before the error is held.
APPX
230
Appendix 3 Remote Buffer Memory