6.2

Parameter Settings for CC-Link IE Field Network

When the NZ2GN-GFB is used as the CC-Link IE Field Network local station, configure the settings described in this section.
Set the parameters of CC-Link IE Field Network with the network parameters written to the CPU module of the CC-Link IE
Field Network master station.
For the setting procedure for the master station, refer to the following.
 User's manual for the master station used
Network configuration setting
The following shows the NZ2GN-GFB items set in network configuration settings.
■Setting procedure
1.
Open the "CC-Link IE TSN Configuration" window from the parameter of CC-Link IE Field Network master station.
[Navigation window]  [Parameter]  [Module Information]  Model name  [Basic Settings]  [Network Configuration
Settings]
2.
Select a general local station in "Module List" and drag it to the list of stations or the network map.
3.
An assignment setting row is added to the station list, the total number of stations is increased, and the selected module
is added to the network map.
4.
Set items in the station list if necessary.
5.
Click the [Close with Reflecting the Setting] button to complete the setting process and close the window.
■Setting item
Item
STA#
Station Type
*2
RX Setting, RY Setting
Points
Start
End
*2
RWw Setting, RWr Setting
Points
Start
End
Setting
Sets the NZ2GN-GFB station number.
Set the same value as CC-Link IE Field Network station number
setting switch.
Sets the station type.
Sets "Local station" for the NZ2GN-GFB.
Sets the assignment of RX, RY points.
Sets the start number of RX, RY.
Sets the end number of RX and RY points.
Sets the assignment of RWw, RWr points.
Sets the start number of RWw, RWr.
Sets the end number of RWw and RWr points.
Setting range
1 to 120
(Default: Serial number of the added
station)
• Local Station
• Intelligent Device Station
(Default: Local Station)
0 to 2048
(Default: 16)
0000 to 3FF0
(Default: 0000)
000F to 3FFF
(Default: 000F)
0 to 1024
(Default: 8)
0000 to 1FFC
(Default: 0000)
0003 to 1FFF
(Default: 0007)
6 PARAMETER SETTINGS
6.2 Parameter Settings for CC-Link IE Field Network
6
45