Precautions
• If the NZ2GN-GFB is not turned off and on or reset, the system runs using the old parameters.
• If the parameter automatic setting is completed with an error, data link cannot be performed on CC-Link IE TSN. Device
station parameter automatic setting interruption (event code: 00C40) is stored in the event history of the CC-Link IE TSN
master station. Take an action corresponding to the code stored in the device station response code (end code).
Device station response code (end
code)
1C00H, CF44H
Description and cause
A module parameter that cannot be used for the
NZ2GN-GFB is set in the CPU module.
Action
Set the module parameter so that the model name of the
device station set in the network configuration settings
matches the model name of the actual module, and write
that parameter to the CPU module of the CC-Link IE TSN
master station.
6 PARAMETER SETTINGS
6.3 Module Parameter Setting