Slave Station Parameter Automatic Setting - Mitsubishi Electric CC-Link IE-NZ2GNSS2-8D User Manual

Tsn remote i/o module with safety functions
Table of Contents

Advertisement

Slave station parameter automatic setting

Slave station parameter automatic setting writes the parameters of the safety remote I/O module to the CPU module.
The parameters of the safety remote I/O module are saved in the CPU internal memory.
When the safety remote I/O module enters or returns to the network, the parameters of the safety remote I/O module are
automatically set via the master station. The parameters are written to the non-volatile memory of the safety remote I/O
module.
The safety remote I/O module starts data link with the master station after parameter automatic setting.
The status of parameter automatic setting can be checked with the remote register. (Page 137 Parameter automatic
setting status monitor area)
• When the user authentication function of the CPU module is enabled, perform the logon of the user
authentication function in advance. (Page 99 User Authentication Function)
• The parameters of the safety remote I/O module are not saved on the SD memory card.
Parameter setting
Operating procedure
1.
Open the "CC-Link IE TSN Configuration" window.
[Navigation window]  [Parameter]  [Module Information]  Model  [Basic Settings]  [Network Configuration
Settings]
2.
Select the safety remote I/O module in "Module List" and drag and drop it to the list of stations (1) or the network map (2).
"Station Type", "RX/RY Setting", and "RWw/RWr Setting" are automatically input. Change a value as necessary.
(1)
(2)
3.
Select the "Parameter Automatic Setting" check box.
7 SETTINGS
59
7.2 Parameter Setting
7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cc-link ie-nz2gnss2-8teCc-link ie-nz2gnss2-16dte

Table of Contents