Remote output signals sent to CC-Link IE Field Network (RY0 onwards)
■When the NZ2GN-GFB is used as the CC-Link IE Field Network master station
Remote output signal (RY) is the area to write remote output signals sent to CC-Link IE Field Network device stations. (
Page 68 Communications using RX, RY, RWr, and RWw)
The value written in this area is sent to CC-Link IE Field Network device stations.
Device No.
RY0
RY1
RY
(1)
RY(
+ 1)
(1)
RY(
+ 2)
(1)
RY
(2)
RY(
+ 1)
(m-1)
RY(
+ 2)
(m-1)
RY
(m)
m: The "Total number of device stations" set in the module parameter of the NZ2GN-GFB. ( Page 47 Module Parameter Setting)
: The value obtained after deducting 1 from the "RX/RY points" of CC-Link IE Field Network device stations (1st station).
(1)
: The value obtained after deducting 1 from the total number of "RX/RY points" of CC-Link IE Field Network device stations (1st and 2nd stations).
(2)
: The value obtained after deducting 1 from the total number of "RX/RY points" of CC-Link IE Field Network device stations (1st to (m-1)-th station).
(m-1)
: The value obtained after deducting 1 from the total number of "RX/RY points" of CC-Link IE Field Network device stations (1st to m-th station).
(m)
Ex.
When the "RX/RY points" is set to 16 points for the first CC-Link IE Field Network device station and 32 points for the second
in the module parameter of the NZ2GN-GFB
CC-Link IE Field Network device station
1st station
2nd station
■When the NZ2GN-GFB is used as the CC-Link IE Field Network local station
Remote output signal (RY) is the area to write remote output signals sent to the CC-Link IE Field Network master station.
( Page 68 Communications using RX, RY, RWr, and RWw)
The value written in this area is sent to the CC-Link IE Field Network master station.
The points set for "RX/RY Setting" in the NZ2GN-GFB under the network configuration settings of the CC-Link IE Field
Network master station are assigned. ( Page 45 Parameter Settings for CC-Link IE Field Network)
APPX
172
Appendix 1 Remote I/O Signals
Description
Remote output signals sent to CC-Link IE Field Network device stations (1st station)
Remote output signals sent to CC-Link IE Field Network device stations (2nd station)
Remote output signals sent to CC-Link IE Field Network device stations (m-th station)
Device No.
RY0
RY1
RYF
RY10
RY11
RY2F