Mitsubishi Electric CC-Link IE TSN User Manual page 210

Field network bridge module
Table of Contents

Advertisement

RWw/ RWr points (CC-Link IE Field Network device station setting)
■Address
CC-Link IE Field Network device station
1st station
2nd station
3rd station
32nd station
■Description
The assigned points for RWw/RWr of CC-Link IE Field Network device stations are set for each device station. (increments of
4)
The RWw/RWr points that can be set in this area differ depending on the connected device. For details, refer to the manual for
the connected device.
Set this area if the NZ2GN-GFB is used as the CC-Link IE Field Network master station.
It does not need to be configured if NZ2GN-GFB is used as the CC-Link IE Field Network local station. (Any value set is
ignored.)
If the set device station exceeds the number of stations set in the total number of device stations, the set value is not reflected
and ignored.
■Setting value
b15
b14
b13
*1
Fixed to 0
*1 A value set in bit 11 to bit 15 is ignored.
CC-Link IE Field Network device station type
Remote I/O station
Remote device station
Intelligent device station
Local station
Set the value for each range corresponding to the above station types and communication modes in increments of 4.
Set the RWw/RWr points of device stations so that the total does not exceed the maximum number of link points (1 network)
of CC-Link IE Field Network.
To enable a set parameter, refer to the following.
Page 184 Operation condition setting request flag (RWw0.b9)
• If a value outside the configurable range is written and the 'Operating condition setting request flag'
(RWw0.b9) is turned on, an error (error code: 0286H) occurs and all parameters are not saved in the non-
volatile memory of the NZ2GN-GFB. Set it again after correcting the value.
• If the RWw/RWr points are not set in increments of 4, an error (error code: 0295H) occurs and all
parameters are not saved in the non-volatile memory of the NZ2GN-GFB. Set it again after correcting the
value.
• If the total number of RWw/RWr points exceeds the maximum number of link points (1 network) of CC-Link
IE Field Network, an error (error code: 0293H) occurs and all parameters are not saved in the non-volatile
memory of the NZ2GN-GFB. Set it again after correcting the value. ( Page 16 Performance
Specifications)
• If the CC-Link IE TSN Class setting is set to A, set the values so that the total number of "RX/RY points" and
"RWw/RWr points" does not exceed 2048 bytes. ( Page 93 CC-Link IE TSN Class setting function)
APPX
208
Appendix 3 Remote Buffer Memory
b12
b11
b10
b9
Setting value
Address
0013H
001BH
0023H
010BH
b8
b7
b6
b5
Communication mode
Normal/High-speed
Normal/High-speed
Normal/High-speed
Normal
High-speed
b4
b3
b2
b1
Setting range
Fixed to 0000H (fixed to 0)
0000H to 0040H (0 to 64)
0000H to 0400H (0 to 1024)
0000H to 0400H (0 to 1024)
0000H to 0100H (0 to 256)