Mitsubishi Electric CC-Link IE TSN User Manual page 167

Field network bridge module
Table of Contents

Advertisement

Error code
Error definition and causes
D842H
• Routing information to the destination station
network number is not registered.
• In transient transmission, there are over seven
relays to other networks.
D843H
An error was detected in the network module.
D844H
An incorrect frame was received.
• Unsupported pre-conversion protocol
• Unsupported frame type
• Application header variable part
• Application header HDS
• Application header RTP
• Read command not requiring response
D902H
An error was detected in the network module.
D903H
During execution of the communication test, the test
was retried.
D905H
A communication monitoring timeout has occurred
in communication test.
D906H
Transmission completion wait timeout has occurred
in communication test.
D909H
The header information of transient transmission is
incorrect.
D90AH
During execution of the communication test, the test
was retried.
D90BH
The number of stations that communicate in the
network is out of the specification range.
D90CH
The target station specified for the communication
test is incorrect.
D912H
Transient transmission sending has failed.
D913H to D917H
An error was detected in the network module.
D919H
No response from the target station of the
communication test.
DA00H
An error was detected in the network module.
DA01H
An error was detected in the network module.
DA10H to DA17H
An error was detected in the network module.
DA19H
An error was detected in the network module.
Action
• Correct the target network number at the transient request source, and retry the
operation.
• Correct the communication path from the transient request source to the
destination, and retry the operation.
• When the dynamic routing is not used, or the module of the series other than
MELSEC iQ-R is included, retry the operation after correcting the routing setting.
• Change the system configuration so that the number of relay stations may be
seven or less.
Please consult your local Mitsubishi representative.
Correct the request data at the transient request source, and retry the operation.
Please consult your local Mitsubishi representative.
After completion of the communication test, retry the operation.
• Check the network status using the CC-Link IE Field Network diagnostics of the
engineering tool, and take action. Then, retry the operation.
• Check if "Routing Setting" of "CPU Parameter" is correctly set, and take action.
• Check the network status using the CC-Link IE Field Network diagnostics of the
engineering tool, and take action. Then, retry the operation.
• Lower the transient transmission usage frequency, and then perform again.
• When "Communication Mode" in "Application Settings" of the master station
(submaster station) is set to "High-Speed", change it to "Normal" and retry the
operation.
• Check if "Routing Setting" are correctly set.
Correct the header information at the transient request source, and retry the
operation.
Check the network status using the CC-Link IE Field Network diagnostics of the
engineering tool, and take action. Then, retry the operation.
• Check the network status using the CC-Link IE Field Network diagnostics of the
engineering tool, and take action.
• If the number of device stations per network is more than the maximum number
of connectable stations, reduce it so that it does not exceed the maximum
number.
• Correct "Target Station" of communication test, and retry the operation.
• "Communication Test" cannot be executed for own station and relay sending
station.
• Lower the transient transmission usage frequency, and then perform again.
• When "Communication Mode" in "Application Settings" of the master station
(submaster station) is set to "High-Speed", change it to "Normal" and retry the
operation.
• Check if the switching hub and the cables are connected properly.
Please consult your local Mitsubishi representative.
• Change the IP address, station number, or network number of the target station
of the communication test.
• Check if the network configuration setting is correctly set in the master station
within the same network as the target station of the communication test.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
10 TROUBLESHOOTING
165
10.7 Error Code List
10

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cc-link ie

Table of Contents