Mitsubishi Electric CC-Link IE TSN User Manual page 122

Field network bridge module
Table of Contents

Advertisement

Checking station information
Information on the NZ2GN-GFB with established communication is displayed in the "Station Information List" window.
Information on the NZ2GN-GFB, such as the production information, firmware version, and module inherent information, can
be checked by clicking the [Station Information List] button in the "CC-Link IE TSN/CC-Link IE Field Diagnostics" window.
For items displayed in the "Station Information List" window, refer to the following.
 User's manual for the CC-Link IE TSN master station used
The module inherent information of the NZ2GN-GFB shows the statuses of the CC-Link IE Field Network station number
setting switch during startup and function setting switches.
Item
Switch setting status
example
Display of module inherent
information (in
hexadecimal)
Ex.
When the CC-Link IE Field Network station number setting switch is set to 1AH and function setting switch 2 is on, "Module
Inherent Information" shows "01A4".
10 TROUBLESHOOTING
120
10.1 CC-Link IE TSN/CC-Link IE Field Diagnostics
Bit
15
14
13
12
11
0 (fixed)
CC-Link IE Field Network station number setting
switch
 16
1
0
1
10
9
8
7
6
 1
A
A
5
4
3
2
1
Function setting switch
1
2
3
0
1
0
4
0
4
0

Advertisement