RX/RY points (CC-Link IE Field Network device station setting)
■Address
CC-Link IE Field Network device station
1st station
2nd station
3rd station
32nd station
■Description
The assigned points for RX/RY of CC-Link IE Field Network device stations are set for each device station. (increments of 16)
The RX/RY points that can be set in this area differ depending on the connected device. For details, refer to the manual for the
connected device.
Set this area if the NZ2GN-GFB is used as the CC-Link IE Field Network master station.
It does not need to be configured if NZ2GN-GFB is used as the CC-Link IE Field Network local station. (Any value set is
ignored.)
If the set device station exceeds the number of stations set in the total number of device stations, the set value is not reflected
and ignored.
■Setting value
b15
b14
b13
b12
*1
Fixed to 0
*1 A value set in bit 12 to bit 15 is ignored.
Set the value for each range corresponding to the following station types in increments of 16.
Set the RX/RY points of device stations so that the total does not exceed the maximum number of link points (1 network) of
CC-Link IE Field Network.
CC-Link IE Field Network device station type
Remote I/O station
Remote device station
Intelligent device station
Local station
To enable a set parameter, refer to the following.
Page 184 Operation condition setting request flag (RWw0.b9)
• If a value outside the configurable range is written and the 'Operating condition setting request flag'
(RWw0.b9) is turned on, an error (error code: 0285H) occurs and all parameters are not saved in the non-
volatile memory of the NZ2GN-GFB. Set it again after correcting the value.
• If the RX/RY points are not set in increments of 16, an error (error code: 0294H) occurs and all parameters
are not saved in the non-volatile memory of the NZ2GN-GFB. Set it again after correcting the value.
• If the total number of RX/RY points exceeds the maximum number of link points (1 network) of CC-Link IE
Field Network, an error (error code: 0292H) occurs and all parameters are not saved in the non-volatile
memory of the NZ2GN-GFB. Set it again after correcting the value. ( Page 16 Performance
Specifications)
• If the CC-Link IE TSN Class setting is set to A, set the values so that the total number of "RX/RY points" and
"RWw/RWr points" does not exceed 2048 bytes. ( Page 93 CC-Link IE TSN Class setting function)
b11
b10
b9
b8
Setting value
Address
0012H
001AH
0022H
010AH
b7
b6
b5
b4
Setting range
0000H to 0040H (0 to 64)
0000H to 0080H (0 to 128)
0000H to 0800H (0 to 2048)
Appendix 3 Remote Buffer Memory
b3
b2
b1
b0
APPX