Mitsubishi Electric CC-Link IE TSN User Manual page 158

Field network bridge module
Table of Contents

Advertisement

Error code
Error type
3001H
Moderate
error
3601H
Moderate
error
3C00H
Major error
3C01H
Major error
3C0FH
Major error
3C10H
Major error
3C13H
Major error
3C14H
Major error
3C2FH
Major error
3E00H
Major error
*1*2
D000H
Minor error
*1*2
D001H
Minor error
10 TROUBLESHOOTING
156
10.7 Error Code List
Error name
Error definition and causes
CC-Link IE Field
One of the following is detected.
Network Station No.
• There is a station with the same
duplication detection
station number on the same CC-Link
IE Field Network.
• There are multiple master stations
and sub-master stations on the same
CC-Link IE Field Network.
• There is a CC-Link IE Controller
Network (twisted pair cable) station
on the same CC-Link IE Field
Network.
Inter-module
The NZ2GN-GFB is set to
synchronization target
"Synchronous" in the network
mismatch
configuration settings of the CC-Link IE
Field Network master station.
Hardware error
Module hardware error
Hardware error
Module hardware error
Hardware error
Module hardware error
Hardware error
Module hardware error
Hardware error
Module hardware error
Hardware error
Module hardware error
Hardware error
Module hardware error
CC-Link IE Field
An error was detected in the CC-Link IE
Network error
Field Network.
CC-Link IE TSN
Invalid network settings are received.
Communication setting
error 1
CC-Link IE TSN
Network settings that cannot be
Communication setting
handled by the NZ2GN-GFB are
error 2
received.
Action
• Correct the station number or station type of the station
where the error was detected.
• Divide it into CC-Link IE Controller Network (twisted
pair cable) and the network.
• After taking the above action, power off and on or reset
all stations where the error was detected.
In the network configuration settings of the CC-Link IE
Field Network master station, Set the bridge module to
"Asynchronous".
• Power off and on the NZ2GN-GFB.
• If this error occurs again, the possible cause is a
module failure. Please consult your local Mitsubishi
representative.
• Power off and on the NZ2GN-GFB.
• Take measures against noise with a shielded cable for
connection.
• If this error occurs again, the possible cause is a
module failure. Please consult your local Mitsubishi
representative.
• Power off and on the NZ2GN-GFB.
• Take measures against noise with a shielded cable for
connection.
• If this error occurs again, the possible cause is a
module failure. Please consult your local Mitsubishi
representative.
• Power off and on the NZ2GN-GFB.
• Take measures against noise with a shielded cable for
connection.
• If this error occurs again, the possible cause is a
module failure. Please consult your local Mitsubishi
representative.
• Power off and on the NZ2GN-GFB.
• Take measures against noise with a shielded cable for
connection.
• If this error occurs again, the possible cause is a
module failure. Please consult your local Mitsubishi
representative.
• Power off and on the NZ2GN-GFB.
• If this error occurs again, the possible cause is a
module failure. Please consult your local Mitsubishi
representative.
• Power off and on the NZ2GN-GFB.
• If this error occurs again, the possible cause is a
module failure. Please consult your local Mitsubishi
representative.
• Power off and on the NZ2GN-GFB.
• If this error occurs again, the possible cause is a
module failure. Please consult your local Mitsubishi
representative.
• Power off and on the NZ2GN-GFB.
• If this error occurs again, the possible cause is a
module failure. Please consult your local Mitsubishi
representative.
• Check that the model name of the CC-Link IE TSN
device station set in the network configuration settings
of the CC-Link IE TSN master station matches the
model name of the actual device.
• If this error occurs even when the model names match,
the possible cause is a module failure. Please consult
your local Mitsubishi representative.

Advertisement

Table of Contents
loading

This manual is also suitable for: