Error code
Error type
Error name
*1
D010H
Minor error
IP address duplication
detection
*1*2
D011H
Moderate
IP address setting error
error
*1*2
D020H
Minor error
CC-Link IE TSN
Network synchronous
communication setting
error
*1*2
D021H
Minor error
Number of RX/RY
points error
*1*2
D022H
Minor error
RWr/RWw number of
points error
*1*2
D023H
Minor error
Communication cycle
setting error (CC-Link
IE TSN Class B/
1Gbps)
*1*2
D024H
Minor error
Communication cycle
setting error (CC-Link
IE TSN Class B/
100Mbps)
*1*2
D028H
Minor error
Communication cycle
setting error (CC-Link
IE TSN Class A)
*1 This error occurs only once when an abnormality is detected. Before clearing the error, eliminate the cause of error and check that a
data link is established.
*2 When this error occurs, other errors may not occur at the same time. Eliminate the cause of error one by one until a data link is
established.
Error definition and causes
An IP address duplication is detected.
Values that the NZ2GN-GFB cannot use
were set for the IP address and subnet
mask settings.
The network synchronous
communication settings of the NZ2GN-
GFB of the CC-Link IE TSN master
station was set to "Synchronous".
RX/RY have been set with points that
cannot be handled by the NZ2GN-GFB.
RWr/RWw have been set with points
that cannot be handled by the NZ2GN-
GFB.
A communication cycle that cannot be
handled by the NZ2GN-GFB is set while
the NZ2GN-GFB is operating with CC-
Link IE TSN Class B at a
communication speed of 1Gbps.
A communication cycle that cannot be
handled by the NZ2GN-GFB is set while
the NZ2GN-GFB is operating with CC-
Link IE TSN Class B at a
communication speed of 100Mbps.
A communication cycle that cannot be
handled by the NZ2GN-GFB is set while
the NZ2GN-GFB is operating with CC-
Link IE TSN Class A.
Action
Change the IP address so that no IP address duplication
occurs in the access range of CC-Link IE TSN.
After changing the settings, power off and on the NZ2GN-
GFB or reset it.
• Without using the set IP address and subnet mask, the
module is operated based on the previous IP address
and subnet mask.
• The set IP address and subnet mask will not be saved
in non-volatile memory.
• Check the IP address and subnet mask again, and
change the settings to values that the NZ2GN-GFB
can use. After changing the settings, power off and on
the NZ2GN-GFB or reset it.
In the network configuration settings of the CC-Link IE
TSN master station, set the network synchronous
communication settings of the NZ2GN-GFB to
"Asynchronous".
Set 16384 or less for the number of points for RX and RY
in the network configuration settings of the CC-Link IE
TSN master station.
Set 2080 or less for the number of points for RWr and
RWw in the network configuration settings of the CC-Link
IE TSN master station.
For the communication cycle setting of the CC-Link IE
TSN master station, set a value supported by the
NZ2GN-GFB.
For the communication cycle setting of the CC-Link IE
TSN master station, set a value supported by the
NZ2GN-GFB.
For the communication cycle setting of the CC-Link IE
TSN master station, set a value supported by the
NZ2GN-GFB.
10 TROUBLESHOOTING
10.7 Error Code List