Mitsubishi Electric CC-Link IE TSN User Manual page 46

Field network bridge module
Table of Contents

Advertisement

Item
Reserved/Error Invalid Station
Network Synchronous Communication
Communication Period Setting
Station-specific mode setting
CC-Link IE TSN Class
*1 Set the CC-Link IE TSN station number here. Set the CC-Link IE Field Network station number using the CC-Link IE Field Network
station number setting switch. ( Page 28 Settings for CC-Link IE Field Network station number setting switch)
*2 If the station number differs from that of the CC-Link IE TSN station number of the NZ2GN-GFB, communication with different networks
may not be performed.
*3 For the RX setting, RY setting, RWw setting, and RWr setting, set a value in the corresponding setting range. If a value outside the
setting range is set, an error occurs on the network configuration setting window.
*4 If "Network Synchronous Communication" is set to "Synchronous", an error (error code: D020H) occurs or the event code of 00C71 is
registered with the event history of the CC-Link IE TSN master station.
*5 Make sure to set the module parameters after changing station-specific mode settings. ( Page 47 Module Parameter Setting)
Simply changing the station-specific mode setting and writing the parameters in the CC-Link IE TSN master station do not change the
station type in CC-Link IE Field Network of the NZ2GN-GFB.
*6 If a different CC-Link IE TSN Class value than the one set using function setting switch 2 is used, the event code of 00C81 is registered
with the event history of the CC-Link IE TSN master station, and the NZ2GN-GFB does not perform data link.
6 PARAMETER SETTINGS
44
6.1 Parameter Settings for CC-Link IE TSN
Setting
Used to set the NZ2GN-GFB as a reserved station or an error invalid
station on CC-Link IE TSN.
The CC-Link IE TSN Network synchronous communication function is
not supported, so set "Asynchronous".
When multiple communication cycles are set, set the cycle of the
NZ2GN-GFB.
When the communication speed differs between the master station
and the NZ2GN-GFB, the setting range is limited. ( Page 42
Communication Period Interval Setting)
Sets the station type of the NZ2GN-GFB CC-Link IE Field Network.
Sets the CC-Link IE TSN Class of the device for the NZ2GN-GFB.
Set the same value as function setting switch 2. ( Page 29
*6
Function setting switch setting)
*4
*5
Setting range
• No Setting
• Reserved Station
• Error Invalid Station
(Default: No Setting)
• Basic Period
• Normal-Speed
• Low-Speed
(Default: Basic Period)
• Local Station
• Master station
(Default: Local station)
• CC-Link IE TSN Class B
• CC-Link IE TSN Class A
(Default: CC-Link IE TSN Class B)