Mitsubishi Electric CC-Link IE TSN User Manual page 157

Field network bridge module
Table of Contents

Advertisement

Error code
Error type
Error name
0292H
Minor error
Parameter error
(device station RX/RY
points abnormal total
points)
0293H
Minor error
Parameter error
(device station RWw/
RWr points abnormal
total points)
0294H
Minor error
Parameter error
(device station RX/RY
points abnormal unit)
0295H
Minor error
Parameter error
(device station RWw/
RWr points abnormal
unit)
0296H
Minor error
Parameter error (CC-
Link IE TSN station No.
<-> IP address
conversion setting
station No. duplication
error)
0297H
Minor error
Parameter error (CC-
Link IE TSN station No.
<-> IP address
conversion setting IP
address duplication
error)
0298H
Minor error
Parameter error (target
station network No.
setting duplication
error)
0299H
Minor error
Parameter error (CC-
Link IE TSN station No.
<-> IP address
conversion setting IP
address out of range)
02A0H
Minor error
Reset not performed
after setting
parameters
1155H
Minor error
Receive processing
error of transient
transmission
1D01H
Minor error
Control device station
inter-module
synchronization target
mismatch
2220H
Moderate
Parameter error
error
2221H
Moderate
Parameter error
error
Error definition and causes
The total number of "RX/RY points" of
the module parameter of the device
station setting exceeds 16384 points.
The total number of "RWw/RWr points"
of the module parameter of the device
station setting exceeds 2048 points.
"RX/RY points" in the device station
setting of the module parameter is not
set in units of 16 points.
"RWw/RWr points" in the device station
setting of the module parameter is not
set in units of 4 points.
The "Station No." of the module
parameter "CC-Link IE TSN station No.
<-> IP address conversion setting" is
duplicated.
The "IP address" of the module
parameter "CC-Link IE TSN station No.
<-> IP address conversion setting" is
duplicated.
The "Target station network No." of the
module parameter "Routing setting" is
duplicated.
The "IP address" of the module
parameter "CC-Link IE TSN station No.
<-> IP address conversion setting" is
outside the configurable range.
Reset has not been performed after
setting parameters.
Parameters are not changed until the
system has been reset.
Transient transmission could not be
performed successfully because an
error occurred in the receiving process.
Detected a CC-Link IE Field Network
device station that has been set to
perform CC-Link IE Field Network
synchronous communications.
The parameters from the CC-Link IE
Field Network master station could not
be received successfully.
The parameter data of the module
parameter is abnormal.
Action
• The parameters are not reflected in the module.
• Change the total number of "RX/RY points" in the
device station setting so that is does not exceed 16384
points, and set again.
• The parameters are not reflected in the module.
• Change the total number of "RWw/ RWr points" in the
device station setting so that is does not exceed 2048
points, and set again.
• The parameters are not reflected in the module.
• Change the "RX/RY points" in the device station setting
to be in units of 16 points, and set again.
• The parameters are not reflected in the module.
• Change the "RWw/ RWr points" in the device station
setting to be in units of 4 points, and set again.
• The parameters are not reflected in the module.
• Change the "Station No." so that it does not overlap,
and then set it again.
• The parameters are not reflected in the module.
• Change the "IP address" so that it does not overlap,
and then set it again.
• The parameters are not reflected in the module.
• Change the "Target station network No." so that it does
not overlap, and then set it again.
• The parameters are not reflected in the module.
• Change it to a value within the configurable range and
set it again.
• When "CC-Link IE Field Network station type" is
changed, change the CC-Link IE Field Network station
number setting switch to match the setting.
• Power off and on the NZ2GN-GFB or reset it.
• Power off and on the NZ2GN-GFB or reset it.
• Take measures against noise with a shielded cable for
connection.
• If this error occurs again, the possible cause is a
module failure. Please consult your local Mitsubishi
representative.
Set the corresponding module to "Asynchronous" in the
inter-module synchronization settings of the target
station.
• Power off and on the NZ2GN-GFB.
• Take measures against noise with a shielded cable for
connection.
• If this error occurs again, the possible cause is a
module failure. Please consult your local Mitsubishi
representative.
• Reset the parameter and power off and on the NZ2GN-
GFB.
• Take measures against noise with a shielded cable for
connection.
• If this error occurs again, the possible cause is a
module failure. Please consult your local Mitsubishi
representative.
10 TROUBLESHOOTING
10.7 Error Code List