9-4 Setting the Mode
Auxiliary Function Mode
Auxiliary Function Mode includes the alarm clear, analog input automatic offset adjustment,
absolute encoder reset, jog operation, parameter initialization, and front panel lock/release.
Displaying Auxiliary Function Mode
operation
Alarm Clear
This releases the alarm generation status.
Some alarms cannot be released. Refer to "11-3 Alarm List" (P.11-5) for details.
1. Execute alarm clear
operation
9
2. Returning to Auxiliary Function Mode display
operation
9-25
Key
Display example
Key
Display example
Key
Display example
OMNUC G5-SERIES AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
Explanation
The item set for the Default Display (Pn528) is displayed.
Press the
key to display Monitor Mode.
Press the
key 3 times to display Auxiliary Function Mode.
Explanation
Press the
key to enter Alarm Clear Mode.
Press and hold the
key for 5 seconds or longer until
is displayed.
The bar indicator will increase.
Alarm clear will start.
This indicates a normal completion.
will be displayed if the alarm could not be cleared.
Reset the power supply to clear the alarm.
Explanation
Press the
key to return to Auxiliary Function Mode.