Pn633
Absolute Encoder Initial Pulse Regeneration Speed
Setting
1,000 to 3,000
range
 Set the pulse regeneration speed when the initial pulse is output.
 Connection with OMRON controller
For the Host Controller to correctly receive the position from the absolute encoder, the pulse output
from the drive must be set to be completed before the controller's timeout.
Pulse are outputted to a speed equivalent to a motor rotating at a speed specified by this
parameter.
The following values or more are recommended for use.
OMRON controller
CJ1W-NC@@4
CS1W-MC@@@
CV500-MC@@@
C200H-MC@@@
3F88M-DRT141
*1. You can set the timeout setting time on the controller side.
Pn634
Hybrid Vibration Suppression Gain
Setting
0 to 30,000
range
Set the hybrid vibration suppression gain.
In general, set it to the same value as the position loop gain, and finely adjust it based on the
situation.
Pn635
Hybrid Vibration Suppression Filter
Setting
0 to 6,400
range
Set the hybrid vibration suppression filter.
Pn637
Vibration Detection Threshold
Setting
0 to 1,000
range
Set the vibration detection threshold.
If torque vibration that exceeds this setting is detected, the vibration detection warning will occur.
This object is set in units of 0.1% of the rated torque.
Pn638
Warning Mask Setting
Setting
−32,768 to 32,767
range
 Set a mask for warning detection.
 If you set the corresponding bit to 1, the corresponding warning detection will be disabled.
 Refer to "11-2 Warning List" (P.11-4) for details on the setting method.
Precautions for Correct Use
Parameters between Pn700 and Pn800 are not used. Do not change the settings.
OMNUC G5-SERIES AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
Unit
r/min
Pn633
1000
1000
3000
1500
Unit
0.1/s
Unit
0.01 ms
Unit
0.1%
Unit
8-7 Special Parameters
Default
Power OFF
1000
setting
and ON
Default
Power OFF
0
setting
and ON
Default
Power OFF
10
setting
and ON
Default
Power OFF
0
setting
and ON
Default
Power OFF
4
setting
and ON
All
Fully-closed
8
Fully-closed
All
All
Yes