Setting The Ip Address Of The Im 152-1Pn On Profinet Io - Siemens SIMATIC ET 200iSP Operating Instructions Manual

Distributed i/o
Hide thumbs Also See for SIMATIC ET 200iSP:
Table of Contents

Advertisement

Commissioning guideline
3.10 Configuring the Example
9. Depending on the required network connection of the ET 200iSP station:
– Connection to a PROFINET IO system with interface module IM 152-1PN:
– Connection to a PROFIBUS DP master system with interface module IM 152-1DP:
10.You can save the changes in the main menu with Station > Save and compile.
Figure 3-8
3.10.2

Setting the IP address of the IM 152-1PN on PROFINET IO

Requirements
• You have selected the PROFINET configuration.
• A PROFINET IO system is configured at a PN IO interface of the CPU.
Procedure
1. Select the interface module in HW Config.
2. Select the menu command Edit > Object Properties.
50
In the window, look for the row with the label "PN-IO" and highlight it. Right-click on the
row and select Object Properties from the menu. The "Properties-PROFINET IO" dialog
opens. Click the Properties button and in the next dialog, click New. A new PROFINET IO
system is now created. Confirm by clicking OK three times in succession.
In the window, look for the row with the label DP and highlight it. Right-click on the row
and select Object Properties from the menu. The "Properties-PROFIBUS DP" dialog opens.
Click the Properties button and in the next dialog, click New. A new DP subnet with 1.5
Mbps is now created. Confirm by clicking OK three times in succession.
Configuration of the S7-400
Operating Instructions, 11/2022, A5E00247483-AK
ET 200iSP