Commissioning and Diagnostics
7.4 Project Engineering with GSD File and SIMATIC PDM
7. Select the remote I/O object created in the previous step (ET 200iSP), select Insert new
object > Remote I/O module in the shortcut menu. In the following dialog box, enter:
Name: Designation for the module (e.g. 8 DI NAMUR).
Address: Slot of the 1st electronic module in the ET 200iSP station.
Number of "Remote I/O" objects: Number of electronic modules in the ET 200iSP station.
Confirm with "OK". Result: The electronic modules are now displayed in the right-hand pane
of the window.
8. Select the first remote I/O object (electronic module in the left pane of the SIMATIC Manager),
select Open objects in the shortcut menu. In the following dialog box "SIMATIC PDM device
selection" select SIEMENS > ET 200iSP > Modules and confirm with "OK".
9. In the following dialog box, select "Specialist" as the user and confirm with "OK". In this mode,
you can assign parameters. Result: SIMATIC PDM starts.
10.After SIMATIC PDM has been started, select the corresponding electronic module as "Module
type". Then click in one of the gray fields to update the window. Result: The parameters and
I&M of the electronic module are displayed.
11.Now set the parameters of the electronic module. Save the changes with the menu
command File > Save and download the parameters with the menu command Device
> Download to device in the electronic module. Exit SIMATIC PDM.
12.For each of the ET 200iSP objects (electronic modules), proceed as described in points 8 to
11.
Procedure for assigning parameters to the interface module
1. Select the remote I/O object (ET 200iSP in the left pane of the SIMATIC Manager), select Open
objects in the shortcut menu.
In the following dialog box "SIMATIC PDM device selection" select SIEMENS > ET 200iSP
> Header-end and confirm with "OK".
2. In the following dialog box, select "Specialist" as the user and confirm with "OK". In this mode,
you can assign parameters. Result: SIMATIC PDM starts.
3. Now set the parameters of the interface module. Save the changes with the menu
command File > Save and download the parameters to the interface module with the menu
command Device > Download to device. Exit SIMATIC PDM.
Procedure for parameter assignment of all modules of the ET 200iSP
1. Select the remote I/O object (ET 200iSP in the left pane of the SIMATIC Manager), select Open
objects in the shortcut menu.
2. In the following dialog box "SIMATIC PDM device selection" select SIEMENS > ET 200iSP
> Header-end and confirm with "OK".
3. In the following dialog box, select "Specialist" as the user and confirm with "OK".
4. Load all parameters of the modules (menu command File > Full upload to PG/PC).
5. Set the parameters for all required modules. In the left pane of SIMATIC PDM you can navigate
to all modules of the ET 200iSP.
164
Operating Instructions, 11/2022, A5E00247483-AK
ET 200iSP