Insulation tested
Current consumption
Starting current inrush
Power loss of the module
Permitted input power
Output current at ambient temperature up to prod‐
uct version 2 of Power Supply PS
Output current at ambient temperature as of prod‐
uct version 3 of Power Supply PS
Status display
Interrupts
Diagnostic functions
UM = DC 250 V / AC 250 V
For additional information, see certificate IECEx KEM 05.0004
https://www.iecex.com (https://www.iecex.com)
KEMA 04 ATEX2263 INMETRO UL-BR 12.0051
https://support.industry.siemens.com (https://support.industry.siemens.com)
up to product version 2: Tolerance rangeDC 20 V to 30 V, protection version 3 and higher Tolerance
1
range DC 19.2 V to 30 V.
Protection with automatic circuit breaker 6 A and tripping characteristic C (per ET 200iSP station)
Rated current: 3.3 A (for DC 24 V)
2
You can find additional information about power loss in the section Restricted Number of Connectable
3
Electronics Modules (Page 70)
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK
Power failure buffering power bus
Voltage failure backup interface module
Power failure buffering backplane bus
between supply voltage and all output voltages DC 600 V
from power supply L+
for DC 24 V
from -20 °C to +60 °C with horizontal mounting
and
-20 °C to +40 °C with all other mounting posi‐
tions
from +60 °C to +70 °C with horizontal mounting Max. 3.5 A
from -20 °C to +70 °C with horizontal mounting
and
-20 °C to +50 °C with all other mounting posi‐
tions
Group error display
Diagnostic information can be read
Technical specifications
Voltages, currents, electrical potentials
min. 0.25 ms
min. 15 ms
min. 0.25 ms
max. 4 A
24.8 A
20 W
Max. 78.6 W
max. 5 A
max. 5 A
Status, interrupts, diagnostics
Yes (on interface module)
No
No
Ys (via interface module)
Safety data
11.1 Power supply PS 24 VDC