Commissioning and Diagnostics
7.13 Diagnostics with STEP 7 with PROFIBUS
Channel-related diagnostics
The maximum number of channel-related diagnostics is limited by the maximum total length of
the device diagnostics of 96 bytes with IM 152-1DP. The length of the device diagnostics
depends on the number of channel-related diagnostics currently present. If there are more
channel-related diagnostics than can be shown in the device diagnostics, bit 7 "Diagnostics
overflow" is set in station status 3.
Table 7-36
Byte
Byte x
Byte x+1
Byte x+2
Byte x+3
... x+5
... up to max. byte 95 for IM 152-1DP
Error types of the electronic modules
See Error types of the electronic modules with PROFIBUS (Page 209).
208
Configuration of the channel-related diagnostics from byte 25 (without deselection of the
diagnostics in the configuration)
7
6
5
4
3
2
1
1
0
0
Description
Bit 0 to 5: 00001
to 100010
B
module that supplies channel-related diagnostics
(Example: Slot 4 has the identification number 3; slot 5 has
the identification number 4, etc.)
Bit 6 and Bit 7: Code for channel-related diagnostics (for
00
, see section "Interrupts in PROFIBUS (Page 212)")
B
Bit 0 to 5: 00000
to 11111
B
channel group that provides diagnostics
Bit 6 and Bit 7: Input/output:
01
: Entry
B
10
: Output
B
11
: Input/output
B
Bit 0 to Bit 4: Error type according to PROFIBUS standard
Bit 5 to bit 7: Channel type
001
: Bit
B
010
: 2 bit
B
011
: 4 bit
B
100
: Byte
B
101
: Word
B
110
: 2 words
B
Next channel-related diagnostic message (assignment like
byte x to x+2)
Operating Instructions, 11/2022, A5E00247483-AK
: Identification number of the
B
: Number of the channel or
B
ET 200iSP