Firmware Update Of The Im 152-1Pn - Siemens SIMATIC ET 200iSP Operating Instructions Manual

Distributed i/o
Hide thumbs Also See for SIMATIC ET 200iSP:
Table of Contents

Advertisement

8.7

Firmware update of the IM 152-1PN

Properties
• After (compatible) function extensions, security updates or performance improvements, you
should upgrade (update) the interface module to the latest firmware version.
• You can obtain the most recent firmware versions from your Siemens representative, or
download it from the Internet at: http://www.siemens.com/automation/service&support
(https://www.siemens.com/automation/service&support)
Tip:
– Before updating, note down the current version of your firmware. You can read out the
– If you encounter problems with the new firmware, you can also download the previous
• The firmware update is performed by the PG/PC via network using the CPU.
Requirements
NOTICE
Requirements for the firmware update of the fail-safe electronic modules
• The F-CPU must be in the "STOP" operating state.
• The supply voltage of the respective fail-safe electronic module is connected.
Note
Updating electronic modules in IO redundancy
If the firmware of two redundantly operating electronic modules is to be changed, note the
following:
The update of the second electronic module must not be started until the electronic module that
was updated first is fully operational again.
Readiness for operation is displayed in the input address space on a channel-specific basis (value
status QI = good).
• You are familiar with the general procedure for updating the firmware.
• A connection to the IO device is possible.
• The storage location of the file for the firmware update is known.
Procedure
1. Open the hardware configuration.
2. Select the electronic module in the device view.
3. In the shortcut menu, select the "Online & Diagnostics" menu command.
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK
version with HW Config.
(current) firmware from the Internet and transfer it to the interface module again.
The engineering system is open.
8.7 Firmware update of the IM 152-1PN
Maintenance