Commissioning and Diagnostics
7.4 Project Engineering with GSD File and SIMATIC PDM
Requirements
• The required software was installed on the PG/ PC or PCS 7 ES.
• You need the GSD file.
– PROFINET GSD file xxx-GSD-FILE
– PROFIBUS GSD file: SI028110.GSG
You can download these on the Internet from Service & Support
automation/service&support).
The GSD file is integrated into the configuration software as described below:
Note
The GSD file for the ET 200iSP is based on revision 4. Result: Not all parameters are available
in COM PROFIBUS.
Make sure that your configuration tool supports GSD files as of revision 4; all parameters will
then be available.
STEP 7 as of V4.02
1. Star STEP 7 an call in HW Config the menu com‐
2. In the following dialog, select the GSD file to be
• A suitable interface is required so that you can work online with SIMATIC PDM:
– For PROFINET IO: Standard access of the configuration tool to the AS and further to the IO
– For PROFIBUS DP e.g., CP5611 (6GK1561-1AA00). The CP must be set to the PROFIBUS DP
162
mand Options > Install new GSD file.
installed and confirm with OK.
The ET 200iSP is displayed in the hardware cat‐
alog in the following directory:
– PROFINET GSD integrated:
In the PROFINET IO directory
– PROFIBUS GSD integrated:
In the PROFIBUS DP directory
device
interface (in the SIMATIC manager: Menu command Options > Set PG/PC interface).
WARNING
Configuration with GSD file and SIMATIC PDM
If you configure the GSD file and SIMATIC PDM, then you create the configuration in 2 steps:
1st step: Configuring by means of GSD file
2nd step: Parameter assignment with SIMATIC PDM
Make sure that the configuration (1st step) is consistent with the parameter assignment
with SIMATIC PDM (2nd step). The assignment of the slots from step 1 must match the
parameters generated from SIMATIC PDM (step 2).
(https://www.siemens.com/
COM PROFIBUS as of V5.0
1. Copy the GSD file from ET 200iSP to the COM
PROFIBUS directory: ...COMPB5\GSD (default
setting). Copy the bitmap file to the directo‐
ry ...COMPB5\BITMAPS.
2. Start COM PROFIBUS and call the menu com‐
mand File > Read GSD file.
The ET 200iSP is displayed in the hardware cat‐
alog during the device configuration.
Operating Instructions, 11/2022, A5E00247483-AK