Maintenance

8.10 Resetting the IM 152-1PN to factory settings using STEP 7

The service data can be read out from the following FW version of the interface module:
• PROFINET IM 152-1PN: As of FW version V1.0.0
• PROFIBUS IM 152-1DP: As of FW version V2.0.5
You can read out the service data with the menu command "PLC -> Save service data", save it in a
file and forward it to Customer Support.
Requirements
You must have STEP 7 as of V5.3 installed to use this function.
Note the following:
• If possible, save the service data immediately after the ET 200iSP station has failed.
• Establish a network connection to the interface module:
– Connection via media converter and PROFINET IO to the IM 152-1PN
– Direct connection via RS 485-IS coupler and PROFIBUS RS 485-IS to the IM 152-1DP
• In the redundant configuration, it is sufficient to establish the connection to one of the two
interface modules.
Procedure
1. In the SIMATIC Manager, select "PLC > Show accessible devices".
2. Select the affected station.
3. Select the "PLC > Save service data" menu command.
In the next dialog box, select the file path and the file names for the service data.
4. Save the file.
5. Forward these files to Customer Support on request.
8.10
Resetting the IM 152-1PN to factory settings using STEP 7
Requirements
• There is a direct connection to the interface module.
• The configuration tool is open.
236
Note
Connect the PG to the PROFIBUS DP and access the IM 152-1DP via the RS 485-IS coupler
(of the intrinsically safe PROFIBUS RS 485-IS).
Operating Instructions, 11/2022, A5E00247483-AK
ET 200iSP