Rules for the configuration of the ET 200iSP in Zone 1
If you use the ET 200iSP in zone 1, then you must observe the following rules:
1. Install the ET 200iSP in an enclosure with degree of protection Ex e (increased safety) (see
section "Installation rules (Page 101)", see Appendix "Article numbers (Page 419)").
2. Disconnection of the PROFINET IO through the media converter (SCALANCE X 212-2 (see
Appendix "Article numbers (Page 419)") with optical safe transceiver. The media converter
guarantees protection in hazardous areas according to EN/IEC 60079-28. You can install the
media converter in the hazardous area of Zone 2 or in the safe area.
3. You can use normal PROFINET IO bus cables in hazardous areas (see Appendix "Article
numbers (Page 419)"). However, you must mark these as "Ex i bus cables" (e.g. attach blue
tape/blue shrink-on sleeve on the ends; mark the cable with blue color).
4. Connecting the fiber-optic cable to the IM 152-1PN using the LC plug (see Appendix "Article
numbers (Page 419)").
The maximum length of the PROFINET IO via fiber-optic cable is 3000 m.
Figure 4-2
Rules for configuration of the ET 200iSP in Zone 21
If you use the ET 200iSP in zone 21, then you must observe the following rules:
1. Install the ET 200iSP in a dust-proof (certified) enclosure with at least degree of protection
IP6X (according to directive 2014/34/EU for category 2D). Additional requirements (surface
temperature, for example) can be found in the certification document for the enclosure (see
section "Installation rules (Page 101)", see Appendix "Article numbers (Page 419)").
2. See points 2 to 4: Rules for the configuration of the ET 200iSP in Zone 1
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK
ET 200iSP configuration Options in Zone 1
Configurations (principle)
4.4 Rules for operation in hazardous areas
63