Siemens SIMATIC ET 200iSP Operating Instructions Manual page 163

Distributed i/o
Hide thumbs Also See for SIMATIC ET 200iSP:
Table of Contents

Advertisement

Procedure for configuring
STEP 7 as of V4.02
1. Start the SIMATIC Manager.
2. Integrate the GSD file into HW Config (see re‐
3. Configure the ET 200iSP with HW Config.
4. Save the configuration or download this to the
Procedure for parameter assignment of electronic modules
1. Start the SIMATIC Manager.
2. Select the process device network view as the default view using the menu
command Options > Settings > View > Process network view.
3. Create a new project with the menu command File > New. In the "New" dialog box that
appears, enter the desired project name and confirm the entry with "OK".
4. Now select the networks symbol, choose Insert new object > PC and Insert new object in
the shortcut menu
– PROFINET IO: PROFINET IO system.
– PROFIBUS DP: PROFIBUS DP master system.
5. In the left-hand pane of the window, select the PC icon. An icon labeled DP Interface now
appears in the right-hand pane of the window. Select it and choose "Object properties" in the
shortcut menu.
In the dialog box, select "PROFIBUS DP networks" under networks and confirm with "OK".
6. Select the network to which you want to connect the ET 200iSP.
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK
quirements).
– Create a new project
– Drag modules from the hardware catalog to
the configuration table
station of ET 200iSP.
Action
PROFINET
In the shortcut
Insert new object > PROFINET IO.
menu, select
In the following di‐
Name:
alog box, enter:
Designation of the ET 200iSP sta‐
tion (e.g. ET 200iSP).
Address:
PROFINET IO address that you have
set on the interface module.
Subnet mask:
Parameters of the network on the
IO controller
Confirm with "OK".
The right part of the window displays the new ET 200iSP station.
7.4 Project Engineering with GSD File and SIMATIC PDM
COM PROFIBUS as of V5.0 or other configuration
software
1. Start COM PROFIBUS or the configuration soft‐
ware.
2. Integrate the GSD file into COM PROFIBUS or the
configuration software (see Requirements).
3. Configure the ET 200iSP with COM PROFIBUS or
the configuration software.
4. Save the configuration and download the con‐
figuration to the DP master.
PROFIBUS
Insert new object > Remote I/O.
Commissioning and Diagnostics
Name:
Designation of the ET 200iSP sta‐
tion (e.g. ET 200iSP).
Address:
PROFIBUS address that you have set
on the interface module.
Number of "Remote I/O" objects:
Number of ET 200iSP stations that
you parameterize.
163