Uninstalling the Power Supply PS
1. Operate the slide with the 4.5 mm screwdriver on the bottom of the terminal module TM-PS-
A or TM-PS-B and pull it downward until it engages.
2. Swivel the power supply out of the bearing position of the terminal module TM-PS-A or TM-
PS-B.
6.5.3

Inserting and labeling the interface module and electronic modules

Installing and labeling interface module and electronic modules
1. Hang the interface or electronic module on the top of the bearing position of the terminal
module.
2. Swing the interface or electronic module down until it latches onto the terminal module.
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK
6.5 Inserting and labeling the power supply, interface module, and electronic modules
CAUTION
Danger of burns
The enclosure of the power supply PS can reach a temperature of up to 90 °C during
operation. There is a danger of burning!
WARNING
Death or serious injury may occur if the following precautions are not taken.
If a power supply is disconnected too early, sparking could cause an explosion.
After unlocking a power supply of the ET 200iSP, wait at least 2 minutes before removing
the power supply in a potentially explosive atmosphere.