Network interface module
12.2 PROFIBUS interface module IM 152-1DP
Article number
CE mark
Use in hazardous areas
•
•
Dimensions
Width
Height
Depth
Weights
Weight, approx.
Bus protocol
Interface
Manufacturer's ID
PROFIBUS addresses
Time stamping
•
Acyclic functions
•
•
Electrical isolation
•
•
See EC type-examination certificate
Maximum values for PROFIBUS RS 485-IS interface:
U
o
I
o
286
ATEX marking
ATEX certificate
Message buffer
Diagnostics
Data records
Between the backplane bus and electronic com‐
ponents
Between PROFIBUS RS 485-IS and electronics
6ES7152-1AA00-0AB0
Yes
II2 G Ex ib IIC T4 and I M2 Ex ib I
04 ATEX 1243
30 mm
129 mm
136.5 mm
245 g
Technical specifications
Module-specific data
PROFIBUS RS 485-IS
RS 485 (intrinsically safe)
8110
1 to 125 permitted
Yes (only for STEP 7)
15 message buffers each for 20 messages
Yes
Yes
Yes
Voltages, currents, electrical potentials
No
Yes
Safety data
KEMA 04 ATEX1243
INMETRO
UL-BR 12.0067
For additional informa‐
tion, see certificate IE‐
CEx KEM 05.0005
± 3.9 V
±136 mA
H
Service & Support
(https://
www.siemens.com/
automation/
service&support)
https://www.iecex.com
(https://
www.iecex.com)
Operating Instructions, 11/2022, A5E00247483-AK
ET 200iSP