12.3 Description of the parameters for the interface modules
12.3.4

Diagnostic interrupts

Description
You can use this parameter to enable or disable diagnostic interrupts ("main switch" for the
ET 200iSP). Diagnostic interrupts are only supported if the ET 200iSP is in S7 DP or DPV1 mode.
12.3.5

Hardware interrupts

Description
You can use this parameter to enable or disable hardware interrupts ("main switch" for the
ET 200iSP). Hardware interrupts are only supported if the ET 200iSP is in S7 DP or DPV1 mode or
with PROFINET.
12.3.6

Time stamping / edge evaluation

Description
The description for time stamping can be found in section "Fundamentals of Time Stamping
(Page 89)".
12.3.7

Data format

Description
This parameter displays the data format of all electronic modules of the ET 200iSP.
12.3.8

Noise suppression

Description
The frequency of your alternating voltage system can affect measured values negatively,
particularly in the case of both measurements in small voltage ranges and thermocouples. Enter
here the line frequency prevailing in your plant (50 Hz or 60 Hz).
The interference frequency suppression parameter is valid for all analog electronic modules. The
integration time and conversion time of the individual modules are also set by means of this
parameter.