Commissioning
12.4 Procedure for commissioning the ET 200MP distributed I/O system
12.4
Procedure for commissioning the
ET 200MP distributed I/O system
12.4.1
Commissioning the ET 200MP for PROFINET IO
Introduction
The commissioning of your automation system depends on the plant configuration.
Commissioning procedure
To commission the ET 200MP as IO device for PROFINET IO, proceed as follows:
Table 12- 2
Step
1
2
4
5
6
7
8
9
10
Note
The operating mode transitions for the IO controller from RUN to STOP or from STOP to RUN
can take several milliseconds, until the mode transition for the inputs and outputs of all
I/O modules for the ET 200MP station is completed. This delay also applies to isochronous
mode.
262
Procedure for commissioning the ET 200MP as an IO device for PROFINET IO
Procedure
Install ET 200MP
Connect ET 200MP
•
Supply voltages
•
PROFINET IO
•
Sensors and actuators
Configure IO controller
Switch on supply voltages for the
IO controller
Switch on supply voltages for
IO devices
Download configuration to the
IO controller
Switch IO controller to RUN mode
Check LEDs
Test inputs and outputs
See...
Section Installation (Page 125)
Section Wiring (Page 148)
CPU manual or documentation of the IO controller
CPU manual or documentation of the IO controller
Interface module
(https://support.automation.siemens.com/WW/view/en/6
7295970/133300) manual
STEP 7 online help
CPU manual or documentation of the IO controller
Interface module
(https://support.automation.siemens.com/WW/view/en/6
7295970/133300) manual
The following functions are helpful: Monitoring and
modifying tags, testing with program status, forcing,
modifying the outputs. See section Test and service func-
tions (Page 328)