Network interface module

12.1

PROFINET interface module IM 152-1PN

Article number
6ES7152-1BA00-0AB0
Properties
The interface module IM 152-1PN has the following properties:
• Operation as IO device
• Preparing the data for the installed electronic modules
• The PROFINET IO configuration can be set via the network.
• Switching off the DC 24 V supply voltage at the terminal module TM-PS-A also switches off
the interface module.
• The maximum address space is 244 bytes for inputs and 244 bytes for outputs.
• Update firmware via PROFINET IO
• Redundancy
• Connecting the station of the ET 200iSP to PROFINET IO via fiber-optic cables (up to 3 km in
length)
• Redundant connection (MRP, S2, R1 system redundancy)
• Backing up the parameters of the electronic modules:
– The parameters / data are saved in the interface module.
• Startup
– After switching on the power supply of the station, the interface module distributes the
– Next, the connection to the network is enabled and the automation system is
– Only when the station exchanges data with the IO controller are the substitute values (of
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK
saved parameters/data to the electronic modules (e.g. substitute values for the output
modules).
commissioned by the IO controller.
the flash memory) replaced with the actual data of the IO controller.