7.5 Assigning Parameters For The Et 200Isp During Operation Using Simatic Pdm - Siemens SIMATIC ET 200iSP Operating Instructions Manual

Distributed i/o
Hide thumbs Also See for SIMATIC ET 200iSP:
Table of Contents

Advertisement

6. Save the changes (menu command File > Save) to update the file.
7. Load all parameters into the modules (menu command Device > Full download to device).
Exit SIMATIC PDM.
Reference
You can find additional information on the parameter assignment in the documentation and
online help of SIMATIC PDM.
7.5
Assigning Parameters for the ET 200iSP during Operation using
SIMATIC PDM
Properties
• You can configure the modules during operation using SIMATIC PDM. Each new parameter
assignment that is correct is applied by the module and retentively stored.
• Incorrect parameters are ignored. The module remains in the previous configuration state.
• Restarting the modules (after supply voltage of the ET 200iSP off ---> on) results in the
currently retentively stored configuration being applied in the modules: LED "SF" of the
electronic modules off
• Applying the retentively stored configuration in the modules is independent of the
communication of the ET 200iSP to the higher-level component (IO controller/DP master).
• The outputs of the modules are controlled by the higher-level components (IO controller/
Class 1 DP master).
Requirements
• PROFINET: SIMATIC PDM as of V9.2.2 (integrated or "stand alone" version)
• PROFIBUS: SIMATIC PDM as of V6.0 (integrated or "stand alone" version)
Procedure for re-configuration
1. Start SIMATIC PDM.
2. Open the project.
3. Switch the view in the SIMATIC Manager: Menu command View > Process Network View.
4. Select the desired ET 200iSP module in the left part of the window. Select "Open objects" in
the shortcut menu. Result: SIMATIC PDM starts.
5. Load the parameters and/or I&M of the module into the PG/PC.
6. Change the parameters and/or I&M.
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK

7.5 Assigning Parameters for the ET 200iSP during Operation using SIMATIC PDM

Commissioning and Diagnostics