Digital electronic module 2 DO Relay UC60V/2A

Parameters 2 DO Relay UC60V/2A
Table 13-19
Parameters for 2 DO Relay UC60V/2A
Parameters
Response to CPU/ master STOP
Substitute value
13.6

Description of the parameters of the digital electronic modules

13.6.1

Time stamping

Description
With this parameter you can enable time stamping channel by channel for each digital input of
the module. The time stamps are passed on from the ET 200iSP to the S7-400 or to the OS if you
also enable the "Time stamping" parameter in the IM 152-1DP.
Time stamping is only allowed for IM 152-1DP. Time stamping is not supported for IM 152-1PN.
13.6.2

Pulse stretching

Description
Pulse extension is a function for changing a digital input signal. A pulse at a digital input is
extended to at least the configured length. If the input pulse is already longer than the
configured length, then the pulse will not be changed.
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK
13.6 Description of the parameters of the digital electronic modules
Range of values
Use substitute value
Keep last value
0
1
Digital electronic modules
Default
Use substitute value
0
Applicability
Channel
Channel