Siemens SIMATIC ET 200iSP Operating Instructions Manual page 296

Distributed i/o
Hide thumbs Also See for SIMATIC ET 200iSP:
Table of Contents

Advertisement

Digital electronic modules
13.1 Digital electronics module 8 DI NAMUR
Note
Address space assignment
The occupied address range of the process image of the 8 DI NAMUR depends on the
configuration. For more information on this, refer to Digital input module (Page 435)
Pin assignment NAMUR changeover contact or encoder after DIN 19234 changeover contact
Table 13-2
Pin assignment NAMUR changeover contact or encoder after DIN 19234 changeover contact
Pin assignment and view
296
Remarks
Changeover contact 1:
Channel 0: Terminals 1 and 2
Channel 1: Terminal 5
Changeover contact 2:
Channel 2: Terminals 9 and 10
Channel 3: Terminal 13
Changeover contact 3:
Channel 4: Terminals 3 and 4
Channel 5: Terminal 7
Changeover contact 4:
Channel 6: Terminals 11 and 12
Channel 7: Terminal 15
DI: Input signal
V
: Sensor supply
S
Operating Instructions, 11/2022, A5E00247483-AK