Commissioning and Diagnostics
7.13 Diagnostics with STEP 7 with PROFIBUS
Error type
10001
10011
10101
10110
10111
11000
11010
11011
11101
11110
210
Error text
17
Encoder- or load
B
D
voltage missing
19
HART communica‐
B
D
tion error (HART di‐
agnostics)
21
Reference channel
B
D
error
22
HART additional
B
D
status available
(HART warning)
23
Reserved for HART
B
D
(HART warning)
24
Actuator discon‐
B
D
nection
26
External fault
B
D
27
HART configura‐
B
D
tion modified
(HART warning)
29
HART main varia‐
B
D
ble outside of the
limits (HART diag‐
nostics)
30
HART non-primary
B
D
variable outside of
the limits (HART di‐
agnostics)
Meaning
•
Supply voltage at the Power
Supply PS missing or too low
•
Power Supply PS is faulty
•
HARD field device is not re‐
sponding
•
Timing error
•
internal reference junction: TC
sensor module defective or
not present
•
external reference junction
(RTD): Parameters do not
point to the RTD module
---
---
Intrinsically safe switching signal
with 4 DO switched on
•
Encoder error
•
Encoder supply faulty
•
Changeover contact error
•
Actuator error
•
HART field device error
---
---
---
Operating Instructions, 11/2022, A5E00247483-AK
Remedy
•
Check the supply voltage at
the Power Supply PS
•
Exchange the Power Supply
PS
•
Check the process wiring
•
Correction of the configura‐
tion
•
Exchanging or connecting
the TC Sensor Module
•
Correction of the configura‐
tion
---
---
---
•
Replacement of encoder/
actuator/HART field device
•
Correction of the process
wiring
---
---
---
ET 200iSP