Commissioning and Diagnostics
7.13 Diagnostics with STEP 7 with PROFIBUS
Error type
10001
10011
10101
10110
10111
11000
11010
11011
11101
11110
210
Error text
17
Encoder- or load
B
D
voltage missing
19
HART communica‐
B
D
tion error (HART di‐
agnostics)
21
Reference channel
B
D
error
22
HART additional
B
D
status available
(HART warning)
23
Reserved for HART
B
D
(HART warning)
24
Actuator discon‐
B
D
nection
26
External fault
B
D
27
HART configura‐
B
D
tion modified
(HART warning)
29
HART main varia‐
B
D
ble outside of the
limits (HART diag‐
nostics)
30
HART non-primary
B
D
variable outside of
the limits (HART di‐
agnostics)
Meaning
Supply voltage at the Power
Supply PS missing or too low
Power Supply PS is faulty
HARD field device is not re‐
sponding
Timing error
internal reference junction: TC
sensor module defective or
not present
external reference junction
(RTD): Parameters do not
point to the RTD module
---
---
Intrinsically safe switching signal
with 4 DO switched on
Encoder error
Encoder supply faulty
Changeover contact error
Actuator error
HART field device error
---
---
---
Operating Instructions, 11/2022, A5E00247483-AK
Remedy
Check the supply voltage at
the Power Supply PS
Exchange the Power Supply
PS
Check the process wiring
Correction of the configura‐
tion
Exchanging or connecting
the TC Sensor Module
Correction of the configura‐
tion
---
---
---
Replacement of encoder/
actuator/HART field device
Correction of the process
wiring
---
---
---
ET 200iSP