Analog electronic modules
14.6 Analog electronic module 4 AO I HART
U
= 27.6 V
o
I
= 91 mA
o
P
= 0.63 W
o
C
= 83 μF
o
L
= 3 mH
o
For additional C
https://www.iecex.com (https://www.iecex.com)
KEMA 04 ATEX1250 INMETRO UL-BR 12.0070
https://support.industry.siemens.com (https://support.industry.siemens.com)
Output ranges (rated values)
Wire break depends on current of the load
1
Approvals
ATEX
IECEx
INMETRO
FM
cULus
CCC
UKCA
374
/ L
combinations, see certificate IECEx KEM 05.0012
o
o
Current
R
Technical specifications
Actuator selection data
0 to 20 mA
4 to 20 mA
II 2 G(1) GD and I M2
Ex ib [ia Ga] IIC T4 Gb
Ex ib [ia IIIC Da] IIC T4 Gb
Ex ib [ia/] I Mb
KEMA 04 ATEX 1250
IECEx KEM 05.0012
BR-Ex ib [ia Ga] IIC T4 Gb
R
BR-Ex ib [ia IIIC Da] IIC T4 Gb
BR-Ex ib [ia] I Mb
Class I, Zone 1, AEx ib [ia] IIC T4;
Ex ib [ia] IIC T4
NI, Class I, DIV. 2, GP. A,B,C,D T4
AIS, Class I, DIV. 1, GP. A,B,C,D
Class II, III, GP. E,F,G
Process Cont. Eq. for Use in HAZ.LOC.
Class I, Zone 1, AEx ib [ia] IIC T4
Ex ib [ia] IIC T4
ASSOC APP. CL. I, DIV.2, GP. A,B,C,D
PROVIDING INT. SAFE CIRCUITS FOR
CL. I, GP. A,B,C,D;
CL. II, III, GP. E,F,G
Ex ib [ia Ga] IIC T4 Gb
Ex ib [iaD] IIC T4 Gb
DEKRA 21UKEX0091
Operating Instructions, 11/2022, A5E00247483-AK
0344