Appendix
A.5 Lightning and overvoltage protection
Components of the application example
The following table explains the components of the application example.
Table A-34
Components for overvoltage protection of the application example
Consecutive num‐
ber from the fig‐
ure
Overvoltage suppressors 24 V supply:
DEHNguard DG S 75 FM
Article number 952 091* **
DEHNgap DGP C S FM
Article number 952 035* **
Comb rail MVS 1 2
Article number 900 617* **
Pin terminal STAK 2x16
Article number 900 589* **
Overvoltage suppressors PROFIBUS RS 485-IS lightning
conductor base part BXT BAS EX,
article number 920 301**
Blitzductor module BXT ML2 BD HF EX 6,
Article number 920 538**
Overvoltage suppressor I/Os, depending on the number
of double cores used
Blitzductor base part BXT BAS EX,
Article number 920 301**
Blitzductor module BXT ML4 BD EX 24,
Article number 920 381**
Additional terminal for the shield connection of the bus
line
Equipotential-bonding cable 16 mm
Equipotential-bonding cable 6 mm
* These components are designed for non-hazardous zones. If these units are installed in hazardous area Zone 1, the com‐
ponents must be installed in a certified Ex d enclosure (flameproof encapsulated). For further information and purchase,
contact:
Siemens AG
DF FA SE
Breslauer Straße 4
90766 Fürth
** Direct purchase of components via:
DEHN + SÖHNE GmbH + Co. KG
Hans-Dehn-Str. 1
D-92318 Neumarkt
http://www.dehn.de (https://www.dehn.de)
450
Component
2
Cu
Cu
2
Meaning
Protection against indirect lightning effects and
overvoltages at zone transition 0
2
Protection against indirect lightning effects and
overvoltages at zone transition 0
2
Protection against indirect lightning effects and
overvoltages at zone transition 0
2
Discharging of interference currents
Standardization of reference potentials
Discharging of interference currents