Siemens SIMATIC ET 200iSP Operating Instructions Manual page 348

Distributed i/o
Hide thumbs Also See for SIMATIC ET 200iSP:
Table of Contents

Advertisement

Analog electronic modules
14.2 Analog electronics module 4 AI I 2WIRE HART
Technical specifications
Article number
General information
Product type designation
Input current
Current consumption, typ.
from supply voltage L+, max.
output voltage / header
supply voltage of the transmitters / header
Power loss
Power loss, typ.
Analog inputs
Number of analog inputs
permissible input current for current input (de‐
struction limit), max.
Cycle time (all channels) max.
Technical unit for temperature measurement ad‐
justable
Input ranges (rated values), currents
Cable length
Analog value generation for the inputs
Measurement principle
Integration and conversion time/resolution per
channel
Smoothing of measured values
Encoder
Connection of signal encoders
348
product feature / of the supply voltage for
transmitters / short-circuit proof
supply current / from supply voltage for trans‐
mitter / maximum
4 mA to 20 mA
shielded, max.
Resolution with overrange (bit including
sign), max.
Integration time, parameterizable
Interference voltage suppression for interfer‐
ence frequency f1 in Hz
parameterizable
Step: None
Step: low
Step: Medium
Step: High
6ES7134-7TD00-0AB0
4AI I 2WIRE HART
280 mA
320 mA
Yes
23 mA; per channel
2.7 W
4
90 mA
120 ms; 30 ms basic conversion time x4 channels
with 60 Hz, 50 Hz interference frequency suppres‐
sion
Yes
Yes
500 m
integrating (Sigma-Delta)
13 bit
No
50 / 60 Hz
Yes; in 4 stages
Yes; 1x cycle time
Yes; 4x cycle time
Yes; 32x cycle time
Yes; 64x cycle time
Operating Instructions, 11/2022, A5E00247483-AK
ET 200iSP

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents