Siemens SIMATIC ET 200iSP Operating Instructions Manual page 306

Distributed i/o
Hide thumbs Also See for SIMATIC ET 200iSP:
Table of Contents

Advertisement

Digital electronic modules
13.2 Digital electronics module 4 DO
Pin assignment of actuators
Table 13-8
Pin assignment of actuators
Pin assignment and view
Pin assignment for enhanced performance (only for 4 DO DC17.4V/27mA, 4 DO DC17.4V/40mA)
Table 13-9
Pin assignment for enhanced performance
Pin assignment and view
Note
If the actuator shutdown signal is connected in parallel via terminals 4/8 and 12/16, note that
this signals is interrupted when a 4 DO module is pulled. If "hot swapping" is intended when the
actuator disconnection is activated, the individual modules must be connected directly to the
signal source.
306
Remarks
Actuator terminals:
Channel 0: Terminals 1 and 2
Channel 1: Terminals 5 and 6
Channel 2: Terminals 9 and 10
Channel 3: Terminals 13 and 14
DO: Digital outputs
M: Ground
Remarks
Increased power:
Parallel connection of channel 0 and
channel 1: Jumper from 1 to 5; ac‐
tuator at 2 and 3
Parallel connection of channel 2 and
channel 3 Jumper from 9 to 13; ac‐
tuator at 10 and 11
DO: Digital outputs
M: Ground
Operating Instructions, 11/2022, A5E00247483-AK