Digital electronic modules
13.1 Digital electronics module 8 DI NAMUR
Input current for an unconnected contact
Input delay
Tolerated changeover time for changeover contacts
Parallel connection of inputs
Normal or periodic counting functions
Cascaded counting function
Cascaded counting function
Sensor (max. frequency)
Input frequency
Pulse time
Quantity
Channel
Measuring frequency (GATE time)
Resolution frequency
Input frequency
302
for "0" signal
for signal "1" (channel 0,1)
for signal "1" (channel 2 to 7)
Permissible quiescent current
for "0" to "1"
for "1" to "0"
Quantity
Channel
Quantity
Channel
Pulse-no-pulse ratio
Edge steepness
Line resistance
Max. cable length 20 m
Max. cable length 100 m
Max. cable length 200 m
at GATE time 50 ms
at GATE time 200 ms
at GATE time 1 s
5
Max. cable length 20 m
Max. cable length 100 m
Technical specifications
max. 1.2 mA
typ. 9.5 mA
typ. 7.5 mA
0.5 mA
2.8 ms to 3.5 ms
2.8 ms to 3.5 ms
300 ms
No
Counter
2
0, 1
1
0
1:1
min. 100 ms
R
5 kHz
1 kHz
500 Hz
200 µs
Frequency meter
2
0, 1
50 ms, 200 ms, 1 s
20 Hz
5 Hz
1 Hz
5 kHz
1 kHz
Operating Instructions, 11/2022, A5E00247483-AK
≤ 1 kΩ