2.2
About Installation Environment
To use safely and maintain the reliability, take the followings into consideration:
Install the product where the exhaust heat will not damage surroundings.
This product performs forced air cooling using a fan. Keep the front and rear, on which the air
inlet and outlet are located, away from the wall at least 50 cm to secure air circulation.
This product exhausts the heat from the air outlet on the rear. Do not place heat-sensitive objects
around the outlet.
If you install the product in a closed narrow room, air conditioning equipment is required. The
heat value of this product is shown in Table 2-2.
Model
DP060LM
DP120LM
DP180LM
Note: Estimate at power input single-phase 200 V or three-phase three-wire 200 V or
three-phase four-wire 380 V (phase voltage 220 V), rated output.
Install the product on a sturdy place.
The floor needs to have enough strength to support the weight of this product. The mass of this
product is shown in Table 2-3.
Do not install this product on a sloped surface. The Adjuster Foot is only for temporary fixing,
and cannot support the unit's own weight. You also must not lean on this product or use it as a
support. How to use the Adjuster Foot is shown in Figure 2-1.
Up
Down
Up
Down
There are screw taps for anchor brackets on this product.
DP060LM/DP120LM/DP180LM
Table 2-2 Heat Value
Rated output
6 kVA
12 kVA
18 kVA
Table 2-3 Mass
Model
DP060LM
DP120LM
DP180LM
The Adjuster Foot can be moved up by rotating it counterclockwise and
moved down by rotating it clockwise as viewed from above.
Use an open-end wrench.
(DP060LM / DP120LM: 19mm width, DP180LM:30mm width)
Figure 2-1 How to Use the Adjuster Foot
2.2 About Installation Environment
Heat value
1.8 kW
1550 kcal/h
3.6 kW
3100 kcal/h
5.4 kW
4650 kcal/h
Mass
125 kg approx.
200 kg approx.
350 kg approx.
9