Table 4-5 Simulation Function Steps And Settable Step Parameters - NF DP060LM Instruction Manual

Programmable ac power source
Table of Contents

Advertisement

4. Advanced Operation

Table 4-5 Simulation Function Steps and Settable Step Parameters

Step
Step time
AC voltage
Frequency
ON/OFF
Start phase
ON/OFF
Stop Phase
Trigger output
Sync code
output
Note: "—" means that this parameter cannot be set.
 Start phase (Start Phs)
ON or OFF can be selected for the start phase. When ON is selected, the step starts at the specified
start phase. When OFF is selected, the step starts at the phase in which the previous step ended.
When selecting ON, a numerical entry box in which you can specify the start phase opens.
The start phase can be set at the Normal 1, Normal 2, and Abnormal steps. For other steps, the start
phase is fixed to OFF and cannot be specified.
 Stop phase (Stop Phs)
ON or OFF can be selected for the stop phase. When ON is selected, the step ends at the specified
stop phase. If the phase is not the specified stop phase after the Step Time elapsed, the execution
continues the output of that step until reaching the specified Stop Phase, then performs the next step.
When OFF is selected, the step transitions to the next step when the Step Time has elapsed regardless
of the phase. When selecting ON, a numerical entry box in which you can specify the stop phase
opens.
The stop phase can be set at the Normal 1, Normal 2, and Abnormal steps. For other steps, the stop
phase is fixed to OFF and cannot be specified.
 Trigger output (Trig Out)
State output to CONTROL I/O connector. This specifies whether the trigger output presents when the
step starts. Polarity and pulse width of the trigger output complies with the trigger output setting (see
4.3.5). At the Initial Step, the trigger output cannot be specified and thus no trigger is output.
 Step sync code output (Code)
State output to CONTROL I/O connector. Code to output while the execution of the step, which is
specified by 2-bit H/L. The step synchronization code can be specified also at the Initial Step.
106
Initial
Normal 1
T1
V0
V1
F0
F1
ON/OFF
P0
P1
ON/OFF
Q0
Q1
ON/OFF
S0
S1
Trans 1
Abnormal
T2
T3
V3
F3
ON/OFF
P3
ON/OFF
Q3
ON/OFF
ON/OFF
S2
S3
PROGRAMMABLE AC POWER SOURCE
Trans 2
Normal 2
T4
T5
—(=V1)
—(=F1)
ON/OFF
P5
ON/OFF
Q5
ON/OFF
ON/OFF
S4
S5

Advertisement

Table of Contents
loading